T&P Relief Valve Leaking: Causes, Testing and When to Replace It

The temperature and pressure relief valve is the last safety on a water heater. It opens if the water gets too hot or the pressure gets too high. A standard residential valve is marked 150 psi and 210°F.

Safety: Never plug, cap or valve off a relief valve or its discharge pipe. Watts states plainly that the valve is an emergency safety device and must not be used as an operating control. A heater with a blocked relief valve can explode.

Why it's dripping

Thermal expansion (most common). Water expands when it is heated. If the house has a check valve, backflow preventer or pressure reducing valve on the supply, the expanded water can't push back into the main. Pressure rises until the relief valve opens a little. The tell: it drips while the heater is firing and stops after hot water is used.

High supply pressure. If static pressure is already high, it takes very little expansion to reach the valve's setting.

Overheating. A stuck thermostat or grounded element can drive the tank to the valve's temperature setting. The discharge will be very hot and heavy. Shut the heater off.

A fouled or worn valve. Scale on the seat keeps it from closing. This often starts right after someone lifts the lever on an old valve.

How to sort it out

  1. Thread a pressure gauge with a lazy hand onto the drain valve or a hose bibb.
  2. Note the static pressure with no water running.
  3. Let the heater run a full cycle with no fixtures open and read the high mark.
  • Pressure climbs toward the valve's rating during heating: thermal expansion. Install or service a thermal expansion tank.
  • Static pressure is high all the time: the house needs a pressure reducing valve, and then an expansion tank, because the PRV closes the system.
  • Pressure stays moderate and the valve still weeps: replace the valve.

Testing and reinspection (Watts)

  • Operate the test lever at least once a year to make sure the waterways are clear. Stand clear of the discharge; the water is scalding.
  • If no water flows when the lever is lifted, Watts says to turn the water heater off and call a plumber. The valve is blocked.
  • Have the valve removed and inspected by a licensed plumber at least every three years (some Watts tags say every two to four years). Corrosive water and mineral deposits can stop a valve from working without any outward sign.

Replacing it

  • Match the pressure setting on the old valve and the heater's rating plate. The valve's BTU discharge capacity must be higher than the heater's input.
  • The sensing element has to sit in the water in the top six inches of the tank. Use the extended-shank version where the tank's insulation is thick.
  • Run the discharge pipe the way the code adopted where you work requires: full size, pitched down, no valves or caps, ending where a discharge will be seen and won't hurt anyone.

FAQ

Is it normal for a T&P valve to drip?

No. A drip means pressure or temperature reached the valve's setting, or the valve can't seat. Find out which with a gauge.

Will an expansion tank stop a relief valve from leaking?

If the cause is thermal expansion in a closed system, yes, as long as the tank is sized and precharged correctly.

How often should a T&P valve be tested?

Watts says to operate the lever at least once a year and to have the valve inspected by a licensed plumber at least every three years.

Can I cap the discharge pipe to stop the drip?

Never. Capping it removes the only protection against a tank rupture.