Thermal Expansion Tank Precharge: How to Set It and Test the Tank

A thermal expansion tank gives heated water somewhere to go. Without one, a closed system pushes pressure up every time the heater fires, and the relief valve drips. The tank only works if its air charge matches the house.

Why a system needs one

Amtrol puts the tank between the water heater and whatever closes the system: a backflow preventer, check valve or pressure reducing valve. Any of those stops expanded water from pushing back into the main. The tank's sealed air cushion compresses instead and keeps pressure below the relief valve setting.

Setting the precharge

  1. Measure the cold water supply pressure with a gauge on a hose bibb or the heater drain, with no water running.
  2. With the tank empty of water and not yet connected, take the cap off the air valve.
  3. Check the charge with a tire gauge. Add air with a hand pump or let air out until it matches the supply pressure.
  4. Put the cap back on and tighten it. Amtrol warns that a cap that doesn't seal will let the precharge leak away and the tank will fail.

Amtrol's instructions add extra steps when the precharge has to go above 55 psig. Read the sheet for the model before pumping it higher.

If the house has a pressure reducing valve, set the PRV first, then charge the tank to the pressure downstream of it.

Installing it

  • On the cold supply line to the heater, between the heater and the backflow preventer, check valve or PRV.
  • Amtrol recommends mounting the tank vertically, hanging down.
  • Support it. A tank that has filled with water is heavy, and the tee is not a bracket.
  • Use a tank made for potable water. Amtrol warns that its hydronic Extrol tanks will corrode on domestic water; that is what Therm-X-Trol is for.
  • After filling the system and before firing the heater, open a hot tap until the air is out.

Checking an existing tank

Amtrol's own test is to check the air pressure at the valve.

  1. Shut off the water to the heater and open a hot tap to drop the pressure to zero. A tank read under pressure only tells you the system pressure.
  2. Put a tire gauge on the air valve.
  3. Water at the air valve: the diaphragm has failed. Replace the tank.
  4. Low or no air: the tank has lost its charge. Amtrol says to replace it. If you recharge one, come back and check that it held.

A quick knock test helps too: a good tank sounds hollow on the air side and dull on the water side. One that is dull all over is waterlogged.

Sizing

Amtrol's residential sizing chart is built on 40°F incoming water, a 150 psi relief valve and a precharge equal to static supply pressure. Pick the model from the manufacturer's chart using the water heater's volume and the supply pressure. Higher supply pressure or a hotter setpoint needs a bigger tank.

FAQ

What pressure should an expansion tank be set to?

The same as the cold water supply pressure, measured with no water running.

Can I set the precharge with the tank installed?

Only with the water pressure off and the system drained down to zero at that point. Otherwise the gauge reads system pressure, not the air charge.

How do I know an expansion tank is bad?

Water at the air valve, no air charge with the system at zero pressure, or a relief valve that has started dripping during heating cycles.

Do I need an expansion tank with a PRV?

A pressure reducing valve closes the system, so expanded water can't return to the main. That is the situation the tank is made for, and many codes require one. Check the code adopted where you work.